Water-Spray Test Rack — Calibration Verification
Verifies this rack meets the ASTM E1105-15 spray-rack water-application rate of 5.0 gal/hr/ft²
(E1105 / E331 / E547 spray-rack family; six-month recalibration required). This is a different apparatus and
method from AAMA 501.2, which is a hand-held single-nozzle field hose test run at 30–35 psi — do not
cite 501.2 as the basis for this rack's numbers.
Rack: 4 zones, 1 ft² catch area each (4 ft² total) → minimum 20 gal/hr combined to pass.
Recalibrate every 6 months and before any E1105 water-penetration test.
Rack ID / Serial:
Technician:
Test Date:
Next Calibration Due (+6 mo):
Pre-Test Checklist
All 4 nozzles inspected — no clogging, cracking, or mineral buildup
Water supply confirmed stable (no fluctuation expected during 15-min run)
All 4 catch buckets tared / weighed empty — recorded in table below
Pressure gauge zeroed and functioning; hose connections leak-free
Formula Reference — Follow in Order
1. Net water wt (lb) = Bucket + water wt − Empty bucket wt
2. Volume (gal) = Net water wt (lb) ÷ 8.34 [lb per U.S. gallon — standard water density]
3. Flow rate (gal/hr) = Volume (gal) × 4 [15-min run × 4 = 60 min/hr]
4. Combined total (gal/hr) = Zone 1 + Zone 2 + Zone 3 + Zone 4
5. PASS only if BOTH: (a) Combined total ≥ 20 gal/hr, and (b) EACH zone individually falls between 4–10 gal/hr.
If either fails → clean / inspect / replace nozzles and retest before use on any E1105 test.
2. Volume (gal) = Net water wt (lb) ÷ 8.34 [lb per U.S. gallon — standard water density]
3. Flow rate (gal/hr) = Volume (gal) × 4 [15-min run × 4 = 60 min/hr]
4. Combined total (gal/hr) = Zone 1 + Zone 2 + Zone 3 + Zone 4
5. PASS only if BOTH: (a) Combined total ≥ 20 gal/hr, and (b) EACH zone individually falls between 4–10 gal/hr.
If either fails → clean / inspect / replace nozzles and retest before use on any E1105 test.
Zone Data — Run Duration: 15 min fixed | Target Pressure: 12–15 psi (this rack's setpoint)
| Zone | Empty bucket wt (lb) | Bucket + water wt (lb) | Net water wt (lb) | Volume (gal) | Flow rate (gal/hr) | In 4–10 range? (Y/N) |
|---|---|---|---|---|---|---|
| 1 | ||||||
| 2 | ||||||
| 3 | ||||||
| 4 | ||||||
| COMBINED TOTAL (gal/hr): | ≥20? Y / N | |||||
Each zone's catch area = 1 ft², so the Flow rate (gal/hr) column above equals gal/hr/ft² directly.
Pressure Log (process QC — not the pass/fail metric)
| Time (min) | Gauge reading (psi) | In 12–15 psi range? |
|---|---|---|
| 0 | ||
| 5 | ||
| 10 | ||
| 15 |
Result
PASS
FAIL
Corrective action / notes:
Technician Signature:
Date: